Permit: T08CM02420

Parcel: 117050880


Addresses:

344 N 4TH AV


Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T08CM02420

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
11/17/2008 ELECTRIC - UFER Approved IVRS - Inspection :*
10/10/2008 ELECTRIC - UFER Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. GROUND RODS TO BE MINIMUM 6' APART - NO LESS
2. MAINTAIN WORKING CLEARANCES 110.26
3. SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE
4. CANNOT ENTER THROUGH METER SECTION 330.7 & MANUFACTURES LISTINGS