Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/17/2008 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |
| 10/10/2008 | ELECTRIC - UFER | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. GROUND RODS TO BE MINIMUM 6' APART - NO LESS 2. MAINTAIN WORKING CLEARANCES 110.26 3. SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE 4. CANNOT ENTER THROUGH METER SECTION 330.7 & MANUFACTURES LISTINGS |