Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/29/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/23/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 12/22/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SCREWS MISSING AT PANEL DEAD FRONT 2) WEATHER PROOF COVER PLATE NEEDED UNDER PANEL 3) MAXIMUM FUSE AT FAN UNIT DISCONNECT OF 45 AMPS 4) HANG DISCONNECT VERTICALLY FOR FAN UNIT |