Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - FINAL
Permit Number - T08CM02395
Inspection Description - FIRE - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/12/2010 | FIRE - FINAL | Denied | 1. Weather proof electrical on roof over exit door southeast stairwell. 2. Recoat fire proofing on I-beams west stairwell in the following areas: a. 6th floor 2nd landing b. 5th floor landing c. 3rd floor landing above exit door 3. Need to have all access roadways done |
|
11/12/2010 | FIRE - FINAL | Approved | APPROVED | |
10/13/2010 | FIRE - FINAL | Partial Approval | TEMP C OF O APPROVAL FOR RIBBON CUTTING ON FRIDAY 10/15/2010. NO RENTING OR MOVE IN'S UNTIL ALARM FINAL AND EXITING CORRECTIONS AND SIGNAGE IN STAIRWELLS ARE DONE. | |
10/12/2010 | FIRE - FINAL | Not ready for Inspection | 1. TALKED TO SUPER ABOUT EXIT DOORS EXITING FROM PENTHOUSE FLOOR - ALL EXIT DOORS NEED TO SWING INTO HALLWAY NOT OUTWARD TO ROOF, OCC LOAD IS 215 ACCORDING TO APPROVED PLANS. APPROVED PLANS SHOW DOORS OPENNG OUTWARD, ACCORDING TO SUPER THEY HAD APPROVAL FROM ARCHITECT TO CHANGE DOOR SWINGS, NO APPROVALS FROM BUILDING OR FIRE. (PANIC HARDWARE NEEDED) 2. NEED SIGNAGE IN STAIRWELLS SHOWING WHAT FLOOR YOU ARE ON AND WHAT DIRECTION TO EXIT. |