Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/09/2010 | FIRE - ALARM FINAL | Approved | ||
| 10/13/2010 | FIRE - ALARM FINAL | Partial Approval | 5TH FLOOR PASSED - PHONE LINES PASSED STILL NEED TO DO 24 HOUR STAND-BY TEST |
|
| 10/12/2010 | FIRE - ALARM FINAL | Denied | 1. ANNUNCIATOR PANEL FAILED WHEN SUN HITS ITS SCREEN IS ALL BLACK 2. 5TH FLOOR STROBES FAILED ON EASTSIDE OF BUILDING 3. PHONES LINES FAILED TO WORK - NEED TO TEST 4. NEED TO DO 24 HOUR STANDBY TEST ON BATTERIES |