Permit: T08CM02395

Parcel: 117060940


Addresses:

55 N 5TH AV


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T08CM02395

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/13/2010 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
08/26/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
5TH FLOOR: 1) HYDRO NOT CONNECTED AT NORTH END, FILTER ACCESS BLOCKED NORTH END AND SQUARE TO ROUND NOT INSULATED X2
2) 1ST FLOOR ACCESS DOOR AT F.D.
3) 2ND,3RD & 4TH FLOOR TILES OK
04/08/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) 4TH FLOOR ABOVE CEILING OK
03/17/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) HYDRO MAINS NORTH OF COL. LINE "E" OK ON PRESSURE TEST 100 PSI AND AT 6TH FLOOR TO GROUND
03/09/2010 MECHANICAL - INTERMEDIATE Cancelled IVRS - RI canceled
03/03/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) HYDRO MAINS COLUMN LINE E-SOUTH OK 100 PSI + ALL FLOORS, ROOMS 140 THRU 143 OK FOR ROCK
2) OK FOR ROCK 3RD FLOOR MECH ONLY
02/19/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK FOR SHEETROCK 2ND FLOOR MECHANICAL ONLY
02/03/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TO INSULATE DUCT ON FIRST 3 FLOORS
02/01/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK TO INSULATE CONDENSATE PIPING
2. PROVIDE ACCESS TO EQUIPMENT PER SECTION 306.1 IMC 2006
3. HYDRONIC PIPING IS TO BE HYDROSTATICALLY TESTED PER SECTION 1208.1 2006 IMC
01/14/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TO PROCEED