Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T08CM02395
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/06/2010 | BUILDING - FINAL | Approved | ||
11/12/2010 | BUILDING - FINAL | Partial Approval | NEED LANDING AT SOUTH DOOR FOR ROOF EGRESS NEED ENGINEERING & FIRE FINAL |
|
11/09/2010 | BUILDING - FINAL | Denied | 1) 5 LB MAX PULL ON ANY DOOR 2) NEED TO SEE FIRE-STOP AT LAV, TOILET AND C.O. 3) SIGNAGE @ RAIN WATER SPIGOT "NON-POTABLE DO NOT DRINK" BLACK LETTERS ON YELLOW SIGN IN SPANISH AND ENGLISH. 4) ACCESSIBLE SIGNAGE AT DECK & SIGN SAYING "NOT AN ACCCESSIBLE ROUTE" AT SOUTH EXIT FROM DECK 5) LANDING REQUIRED AT SOUTH EXIT DOOR FROM DECK 6) NEED TO SEE SUMP PUMPS FROM GARAGE WORKING 7) LIBRARY DOOR TO BALCONY MUST HAVE LOCK THAT REQUIRES NO PINCHING, TWISTING OR TIGHT GRASPING 8) PROPER FIRE-STOP REQUIRED AT ALL RESTROOM TO CORRIDOR PLUMBING PENETRATIONS. NEED PLUMBING FINAL NEED FIRE FINAL NEED ENGINEERING FINAL |
|
08/06/2010 | BUILDING - FINAL | Not ready for Inspection | MUST CHECK FIRESTOP AT BATHROOM LAVS DURING FINAL |