Inspection Status: Approved
Inspection History: BUILDING ABOVE CEILING
Permit Number - T08CM02395
Inspection Description - BUILDING ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/07/2010 | BUILDING ABOVE CEILING | Approved | ||
06/24/2010 | BUILDING ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) 1ST FLOOR EXCEPT ALL CEILING GRID REQUIRES WIRES 8" FROM WALL PER CISCA |
|
06/18/2010 | BUILDING ABOVE CEILING | Partial Approval | 5TH FLOOR OK. | |
06/09/2010 | BUILDING ABOVE CEILING | Denied | DATA CABLE INSTALLERS HAVE SERIOUSLY DAMAGED GYP-BOARD FIREWALLS. THERE IS NO WAY TO PROPERLY APPLY FIRESTOP TO HAMMERED OUT PENETRATIONS. | |
04/30/2010 | BUILDING ABOVE CEILING | Partial Approval | HARD-LID FRAMING 2ND AND 3RD FLOORS OK | |
04/20/2010 | BUILDING ABOVE CEILING | Partial Approval | 1ST FLOOR ABOVE CEILING FIRESTOP a) NEED HILTI ENGINER FIELD APPRAISAL FOR ODD SHAPED PENETRATIONS (elongated at cast iron pipe drains). b) T-STAT & CAD 5 CONDUIT PENETRATIONS TO BE SEALED AFTER WIRE IS PULLED. |