Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T08CM02382
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/30/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
10/20/2009 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEE NOTES DATED 5/22/09 AND 6/22/09 OR INSTALL PER MANUFACTURES DRAWINGS AND INSTALLATION INSTRUCTIONS |
|
10/19/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) CONTRACTOR NOT ON SITE |
|
10/06/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
09/30/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROCEED AS DISCUSSED |
|
06/22/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* PROVIDE DETAILED DRAWING ON FIRE DAMPER INSTALLATION APPROVED BY ENGINEER. INCLUDE STRUCTURE DAMPER IS INSTALLED IN |
|
05/22/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) AWAITING APPROVED DETAIL ON 1ST FLOOR FIRE DAMPER INSTALLATION 2) OK FOR CEILING TILES 1ST AND 2ND FLOORS MECHANICAL ONLY |
|
05/19/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* MET WITH JIM MILITELLO, ROBERT SHERRY, HOWARD WOOLSON, ERIC NEWCOMB FACTORY APPROVED AND PROVIDED FLUE EXHAUST DUCT THROUGH ROOF AND PROPERLY FLASHED AND TERMINATED SHOULD BE INSTALLED ON ALL RTU's REFER TO BELOW MENTIONED CODE 5.10.2.4 UPC |
|
05/15/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS ON FIRE DAMPERS 1ST FLOOR UNIT #16 MED. PRESS NOT CONNECTED REFER TO SECTION 503.2.7 I.E.C.C. ALL JOINTS LONGITUDINAL AND TRANSVERSE SHALL BE SEALED GAS FIRED UNITS ON ROOF ARE DESIGNED FOR OUTDOOR APPLICATION NOT FOR USE IN A MECHANICAL ROOM IT IS OUR BELIEF THAT THIS STRUCTURE IS AN ENCLOSURE. ALSO, FLUE EXHAUST MUST BE A MIN. OF 10' FROM ANY OUTSIDE AIR INLET. |
|
05/08/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
05/07/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* PAID CK#4955 1. PROVIDE MIN. 2 STRAPS PER DUCT RUN (TAPS CANNOT SUPPORT DUCT) 2. INSULATE ROUND DUCT AND TAPS 3. PROVIDE SEISMIC RESTRAINTS ON ALL GRILLS 4. FLEX RUNS NEED TAPS INSULATED 5. PROVIDE ACCESS TO J-BOXES 6. PROVIDE ENGINEERS APPROVAL ON FIRE DAMPER INSTALLATION (1ST FLOOR) 7. SEAL CANS TO REGISTERS 8. PROVIDE ACCESS TO TU-#6 SECOND FLOOR |
|
04/17/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* RECEIVED $150.00 FOR AFTER HRS. INSPECTION 4/16/09 CK#004832 MADE OUT TO CITY OF TUCSON 1. RECEIVED CORRECTION LETTERS ON ITEM 2 (1/27/09) 3RD FLOOR OK FOR CEILING TILES MECHANICAL ONLY |
|
01/27/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. VAV 1-9 ACCESS PANEL IS BLOCKED BY SPRINKLER PIPE 2. SUPPORT VAV PER DETAIL 6 M3.1 3. PROVIDE SPECIFICATIONS FOR PROJECT ON NEXT INSPECTION |
|
01/22/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |