Permit: T08CM02382

Parcel: 116192320


Addresses:

310 W ALAMEDA ST


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T08CM02382

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
10/30/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
10/20/2009 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEE NOTES DATED 5/22/09 AND 6/22/09 OR INSTALL PER MANUFACTURES DRAWINGS AND INSTALLATION INSTRUCTIONS
10/19/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) CONTRACTOR NOT ON SITE
10/06/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
09/30/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROCEED AS DISCUSSED
06/22/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
PROVIDE DETAILED DRAWING ON FIRE DAMPER INSTALLATION APPROVED BY ENGINEER. INCLUDE STRUCTURE DAMPER IS INSTALLED IN
05/22/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) AWAITING APPROVED DETAIL ON 1ST FLOOR FIRE DAMPER INSTALLATION
2) OK FOR CEILING TILES 1ST AND 2ND FLOORS MECHANICAL ONLY
05/19/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
MET WITH JIM MILITELLO, ROBERT SHERRY, HOWARD WOOLSON, ERIC NEWCOMB

FACTORY APPROVED AND PROVIDED FLUE EXHAUST DUCT THROUGH ROOF AND PROPERLY FLASHED AND TERMINATED SHOULD BE INSTALLED ON ALL RTU's REFER TO BELOW MENTIONED CODE 5.10.2.4 UPC
05/15/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS
ON FIRE DAMPERS 1ST FLOOR

UNIT #16 MED. PRESS NOT CONNECTED

REFER TO SECTION 503.2.7 I.E.C.C. ALL JOINTS LONGITUDINAL AND TRANSVERSE SHALL BE SEALED

GAS FIRED UNITS ON ROOF ARE DESIGNED FOR OUTDOOR APPLICATION NOT FOR USE IN A MECHANICAL ROOM IT IS OUR BELIEF THAT THIS STRUCTURE IS AN ENCLOSURE. ALSO, FLUE EXHAUST MUST BE A MIN. OF 10' FROM ANY OUTSIDE AIR INLET.
05/08/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
05/07/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
PAID CK#4955
1. PROVIDE MIN. 2 STRAPS PER DUCT RUN (TAPS CANNOT SUPPORT DUCT)
2. INSULATE ROUND DUCT AND TAPS
3. PROVIDE SEISMIC RESTRAINTS ON ALL GRILLS
4. FLEX RUNS NEED TAPS INSULATED
5. PROVIDE ACCESS TO J-BOXES
6. PROVIDE ENGINEERS APPROVAL ON FIRE DAMPER INSTALLATION (1ST FLOOR)
7. SEAL CANS TO REGISTERS
8. PROVIDE ACCESS TO TU-#6 SECOND FLOOR
04/17/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
RECEIVED $150.00 FOR AFTER HRS. INSPECTION 4/16/09
CK#004832 MADE OUT TO CITY OF TUCSON

1. RECEIVED CORRECTION LETTERS ON ITEM 2 (1/27/09)

3RD FLOOR OK FOR CEILING TILES MECHANICAL ONLY
01/27/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. VAV 1-9 ACCESS PANEL IS BLOCKED BY SPRINKLER PIPE
2. SUPPORT VAV PER DETAIL 6 M3.1
3. PROVIDE SPECIFICATIONS FOR PROJECT ON NEXT INSPECTION
01/22/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*