Permit: T08CM02382

Parcel: 116192320


Addresses:

310 W ALAMEDA ST


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T08CM02382

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/18/2009 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
05/11/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
LEAVE TILE OUT FOR LOW VOLTAGE ON SOUTHWEST CORNER
05/04/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK SOUTH OF NORTH CORRIDOR 2ND FLOOR
04/13/2009 ELECTRIC - ABOVE CEILING Partial Approval 1. OK VAV BOX CONNECTIONS AND ROUGH 3RD FLOOR
OK TO COVER, SUBJECT TO OTHER INSPECTORS APPROVAL
01/27/2009 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. VDV CABLING TO BE AS PER
725.3 & 24, 760.3 & 24, 800.3 & 24, 300.11
2. VERIFY BOX FILL
3. RACEWAYS & BOXES FOR VDV CABLING TO BE PROPERLY SUPPORTED
4. EXPOSED CONDUCTORS & OPEN JUNCTION BOXES AND DANGLING FLEX AND EMT CONDUITS
01/22/2009 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
NO ONE ON SITE TALKED WITH CONTRACTOR
WILL RESCHEDULE FOR MONDAY WHEN RICK HOLLANDER
WILL RETURN