Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/10/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 10/27/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEISMIC SUPPORT SHALL TIE TO STRUCTURE OR GRID MAIN RUNNERS 2. INSULATE BRANCH TAKE OFF's 3. SEAL ALL DUCT 4. ALL BRANCH TAKE-OFF's ARE TO BE HIGH EFFICIENCY 5. PROVIDE MIN. 1X RADIUS ON ALL FLEX BENDS 6. REPAIR INSULATION ON LINE SETS 7. CONDENSATE PIPING IS TO BE INSULATED |
|
| 08/29/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |