Permit: T08CM02377

Parcel: 11003081D

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
11/10/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
10/27/2008 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEISMIC SUPPORT SHALL TIE TO STRUCTURE OR GRID MAIN RUNNERS
2. INSULATE BRANCH TAKE OFF's
3. SEAL ALL DUCT
4. ALL BRANCH TAKE-OFF's ARE TO BE HIGH EFFICIENCY
5. PROVIDE MIN. 1X RADIUS ON ALL FLEX BENDS
6. REPAIR INSULATION ON LINE SETS
7. CONDENSATE PIPING IS TO BE INSULATED
08/29/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*