Permit: T08CM02365

Parcel: 12701004C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM02365

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/29/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/28/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WIRE INSTANT HOT UNDER SINK
2. INSTALL ALL MOUNTING HARDWARE FOR RECEPTACLES IN INDUSTRIAL COVER
3. STRAP MC WITHIN 12" OF SURFACE MOUNTED BOX
4. PROVIDE DETAILED PANEL SCHEDULE
5. PLAN ONLY ALLOWS 4 CURRENT CARRYING CONDUCTORS
IN A COMMON RACEWAY. SEE NOTES.