Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM02365
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/29/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/28/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WIRE INSTANT HOT UNDER SINK 2. INSTALL ALL MOUNTING HARDWARE FOR RECEPTACLES IN INDUSTRIAL COVER 3. STRAP MC WITHIN 12" OF SURFACE MOUNTED BOX 4. PROVIDE DETAILED PANEL SCHEDULE 5. PLAN ONLY ALLOWS 4 CURRENT CARRYING CONDUCTORS IN A COMMON RACEWAY. SEE NOTES. |