Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2008 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 09/24/2008 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHEAR TRANSFER NAILING ON ROOF NEEDS TO BE 8D 6" ON CENTER 2) NEED TO ADD 2X STUD ON INTERIOR SHEARWALL AT DINING ROOM 3) CHANNEL NAILER AT STAIRWALL, NEEDS TO BE SOLID FOR 1 HR FIRE RATING OR 5/8 TYPE X HAS TO GO THRU |