Permit: T08CM02345

Parcel: 141386740

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T08CM02345

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
09/25/2008 FRAMING Approved IVRS - Inspection :*
09/24/2008 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FILL NAIL HOLES IN FHA STRAP TOP PLATES NORTH WALL KITCHEN MINIMUM 16-16D NAILS
2) SEAL PENETRATIONS IN PAPER SOUTH WALL
3) SEAL PAPER IN BEDROOM #2 CLOSET
4) SECURE WIRES NOT OUT OF 2 GANG BOX AT GARAGE SERVICE DOOR
5) NAIL PROTECT WIRES TOP PLATE WEST WALL LAUNDRY
6) NAIL PROTECT WIRES TOP PLATE RIGHT SIDE FRONT DOOR
7) SUPPORT ABS VENT ABOVE HALL BATH MAX 4'
8) NAIL PROTECT BACK HOSE BIB LINE AT TOP PLATES MASTER BED
9) SECURE MASTER BATH CLOSET FLANGE
10) SECURE GLYCOL LINES IN GARAGE WALL