Inspection History: ELECTRIC - PROGRESS
Permit Number - T08CM02339
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/24/2008 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
09/10/2008 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1. (2X4) GRID FIXTURES NEED 2 SCREWS PER FIXTURE INTO GRID IF YOU CAN UTILIZE BEND OUT TABS - PER CODE 2. MC CABLE TO BE SUPPORTED WITHIN 12" OF TERMINATION AND AT 6' INTERVALS PER CODE. |
|
09/09/2008 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE NOTES LAST INSPECTION |
|
09/05/2008 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1. ALL L.V CABLING TO BE SUPPORTED PER CODE OR ABANDONED REMOVE 2. ALL 4/0 BOXES TO BE GROUNDED AND SUPPORTED PER NEC ALSO CHECK FOR CONDUCTOR OVERFILL 3. SUPT. NOT ON SITE AT THIS TIME, ABOVE CEILING INSPECTION |