Permit: T08CM02328

Parcel: 140061050


Addresses:

3626 E FRANKFORT SV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM02328

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/17/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/14/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) NEED GFCI RECEPT IN LIVING ROOM WEST WALL
2) BECAUSE 1" GAS LINE WON'T DELIVER REQUIRED CFH FOR 3 APPLS. OWNER WANTSTO ELIMINATE (GAS FURNACE) INSTALL ROOF TOP ALL ELECTRIC, GAS WOULD THEN BE OK
10/09/2008 ELECTRIC - FINAL Partial Approval 1) SECURE WASHER BOX TO WALL OR VERTICAL PIPE
2) GFCI TO PROTECT LIVING ROOM RECEPTS
3) LEFT GAS DEMAND PIPING CALC. ON SITE. CHECK NUMBER ON INSTANT HOT H20 HTR I USED 215,000 BTU ?. UNDER SIZED WITH GAS RANGE WITHOUT RANGE 268CFH, WITH RANGE 327. PIPE DELIVERS 259
4) GAS PRESSURE TEST OK
5) #14 WIRE ON 20 AMP BREAKERS
6) #8 ROMEX FEEDER IS ONLY GOOD FOR 40 AMPS