Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/17/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/14/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NEED GFCI RECEPT IN LIVING ROOM WEST WALL 2) BECAUSE 1" GAS LINE WON'T DELIVER REQUIRED CFH FOR 3 APPLS. OWNER WANTSTO ELIMINATE (GAS FURNACE) INSTALL ROOF TOP ALL ELECTRIC, GAS WOULD THEN BE OK |
|
| 10/09/2008 | ELECTRIC - FINAL | Partial Approval | 1) SECURE WASHER BOX TO WALL OR VERTICAL PIPE 2) GFCI TO PROTECT LIVING ROOM RECEPTS 3) LEFT GAS DEMAND PIPING CALC. ON SITE. CHECK NUMBER ON INSTANT HOT H20 HTR I USED 215,000 BTU ?. UNDER SIZED WITH GAS RANGE WITHOUT RANGE 268CFH, WITH RANGE 327. PIPE DELIVERS 259 4) GAS PRESSURE TEST OK 5) #14 WIRE ON 20 AMP BREAKERS 6) #8 ROMEX FEEDER IS ONLY GOOD FOR 40 AMPS |