Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T08CM02322
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/20/2009 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/03/2009 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RE-ROUTE CONDENSATE PIPING TO ALLOW ACCESS TO FILTER RACK 2) PROVIDE HANGER SUPPORTS TO AVOID SAGGING OF FLEX DUCT 3) PROVIDE SUPPLY CAN AT RESTROOM 4) APPROVED PLANS MUST BE ON SITE AND AVAILABLE AT ALL TIMES FOR INSPECTIONS |
|
| 07/22/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PROVIDE "MASON SPRING ISOLATORS" PER PLANS ON UNIT HANGERS 2) DRAIN PAN UNDER UNIT NOT SHOWN ON PLANS. PROVIDE E-Z TRAP PER PLANS FOR SECONDARY DRAIN |