Permit: T08CM02322

Parcel: 12216229B


Addresses:

1711 N ALVERNON WY


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM02322

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/23/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/08/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BOND BUSHINGS REQUIRED PER NEC 514.16 AND 501.30A
08/21/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) BONDING RACEWAYS AND ENCLOSURES TO COMPLY WITH 514.16
2) CHECK ALL SEAL OFFS-EXISTING AS WELL AS NEW 501.30 A
08/20/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NEED GUTTER BONDED
NEED TO USE A SEAL ON FEED FOR FREEZER