Inspection History: MECHANICAL - FINAL

Permit Number - T08CM02313

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/20/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
11/18/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
DUCT SMOKE DETECTOR TEST OK X5
AIR BALANCE REPORT OK

1. PROVIDE FACTORY WEATHERPROOF COVER FOR REMOTE CU
2. RTU-2 NOT LEVEL ON CURB
3. HAIL GUARDS BLOCKING DATA PLATES
4. PROVIDE EXTENSION ON HOOD EXHAUST
5. REMOTE CONDENSORS NOT SEALED THROUGH ROOF
6. UNITS NOT PROPERLY LABELED
7. GAS PIPING NOT CONNECTED TO UNITS
8. WASTE VENT TOO CLOSE TO OUTSIDE AIR INTAKE