Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 11/18/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* DUCT SMOKE DETECTOR TEST OK X5 AIR BALANCE REPORT OK 1. PROVIDE FACTORY WEATHERPROOF COVER FOR REMOTE CU 2. RTU-2 NOT LEVEL ON CURB 3. HAIL GUARDS BLOCKING DATA PLATES 4. PROVIDE EXTENSION ON HOOD EXHAUST 5. REMOTE CONDENSORS NOT SEALED THROUGH ROOF 6. UNITS NOT PROPERLY LABELED 7. GAS PIPING NOT CONNECTED TO UNITS 8. WASTE VENT TOO CLOSE TO OUTSIDE AIR INTAKE |