Permit: T08CM02301

Parcel: 12306105A


Addresses:

2131 E DRACHMAN ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/16/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/01/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NEED LABELING PER 690.17
2. SUPPORT CONDUIT AS PER CODE
3. BREAKERS TO BE LISTED FOR USE BY MANUFACTURE
4. GROUNDING ELECTRODE CONDUCTOR TO BE #8 AND INSTALLED AS PER 250.64
5. TIGHTEN ALL LOOSE FITTINGS
6. REVISE PLANS FOR PV DISCONNECT
7. SECURE INVERTER TO STRUCTURE
8. ONLY ONE CONDUCTOR PER TERMINAL LUG

ROOF:
1. NEED CUP WASHER FOR DISSIMILAR METAL AND 3/4 OF A TORN UNDER SCREW
2. REVISE PLANS FOR 24 ARRAYS
3. PROPERLY SUPPORT JUNCTION BOX
4. GROUND JUNCTION BOX
07/24/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no plan or job inspection card on site.| 925*
RANG BELL NO ANSWER.
NEED APPROVED PLANS NEED ACCESS TO ALL EQUIPMENT