Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/16/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/01/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NEED LABELING PER 690.17 2. SUPPORT CONDUIT AS PER CODE 3. BREAKERS TO BE LISTED FOR USE BY MANUFACTURE 4. GROUNDING ELECTRODE CONDUCTOR TO BE #8 AND INSTALLED AS PER 250.64 5. TIGHTEN ALL LOOSE FITTINGS 6. REVISE PLANS FOR PV DISCONNECT 7. SECURE INVERTER TO STRUCTURE 8. ONLY ONE CONDUCTOR PER TERMINAL LUG ROOF: 1. NEED CUP WASHER FOR DISSIMILAR METAL AND 3/4 OF A TORN UNDER SCREW 2. REVISE PLANS FOR 24 ARRAYS 3. PROPERLY SUPPORT JUNCTION BOX 4. GROUND JUNCTION BOX |
|
| 07/24/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no plan or job inspection card on site.| 925* RANG BELL NO ANSWER. NEED APPROVED PLANS NEED ACCESS TO ALL EQUIPMENT |