Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/14/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/05/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
| 12/04/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH #1, 2 & 9 INTERIOR 1. CONTACTOR FOR SUMP PUMP NEEDS TO BE LISTED *RECEIVED LETTER FROM ENGINEER FOR REQUESTED INFORMATION. |
|
| 12/01/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* ROOF: 1. TIGHTEN LOOSE FITTINGS 2. CONDUCTOR COLORS TO BE BROWN, ORANGE, YELLOW 3. BOND BUSHINGS 250.97 4. ONLY ONE CONDUCTOR PER TERMINAL LUG 5. BOND ENCLOSURES 6. MAINTENANCE RECEPTACLE NEEDED 210.65 1. CIRCUIT DIRECTORIES TO BE AS PER 408.4 2. INSTALL COUNTER 3. SHEETMETAL THREAD SCREWS NOT ALLOWED FOR GROUNDING 250.8 4. BOX MORE THAN 1/8" 314.21 ALSO, MORE THAN 1/4 BACK 314.20 5. EXIT LIGHT NOT WORKING 6. NEED ALL SCREWS WITH INDUSTRIAL COVERS 7. SUPPORT CONDUITS THROUGH ROOF 8. PLANS CALL FOR NAMEPLATES AT COOLERS 9. EXTERIOR LIGHTING NOT AS PLANS ALSO INTERIOR 10. EXIT LIGHT TO WAREHOUSE TO BE CIRCUITED PER PLANS |
|
| 11/17/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK LASHING |