Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/14/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/05/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
12/04/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH #1, 2 & 9 INTERIOR
1. CONTACTOR FOR SUMP PUMP NEEDS TO BE LISTED
*RECEIVED LETTER FROM ENGINEER FOR REQUESTED INFORMATION.
12/01/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
ROOF:
1. TIGHTEN LOOSE FITTINGS
2. CONDUCTOR COLORS TO BE BROWN, ORANGE, YELLOW
3. BOND BUSHINGS 250.97
4. ONLY ONE CONDUCTOR PER TERMINAL LUG
5. BOND ENCLOSURES
6. MAINTENANCE RECEPTACLE NEEDED 210.65

1. CIRCUIT DIRECTORIES TO BE AS PER 408.4
2. INSTALL COUNTER
3. SHEETMETAL THREAD SCREWS NOT ALLOWED
FOR GROUNDING 250.8
4. BOX MORE THAN 1/8" 314.21
ALSO, MORE THAN 1/4 BACK 314.20
5. EXIT LIGHT NOT WORKING
6. NEED ALL SCREWS WITH INDUSTRIAL COVERS
7. SUPPORT CONDUITS THROUGH ROOF
8. PLANS CALL FOR NAMEPLATES AT COOLERS
9. EXTERIOR LIGHTING NOT AS PLANS ALSO INTERIOR
10. EXIT LIGHT TO WAREHOUSE TO BE CIRCUITED PER PLANS
11/17/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK LASHING