Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T08CM02269
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/15/2010 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
04/07/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1. BE SURE LV COMPLETE ABOVE ABOVE CEILING ALSO SUPPORT PER NEC. 725-800 2. OK TO CLEAR TEC (CALLED IN TO DENISE @ TEP) 3. CONTR. TO LOCK OUT TAG OUT ELEC. EQUIP. ONLY AUTHORIZED PERSONNEL TO HAVE ACCESS 4. RECEIVED LETTER FROM ENGINEER OF RECORD TO SPECIFY FUSE AT MAIN SERVICE DISCONNECT. |
|
04/01/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) RECEIVED LETTER OF TORQUE FOR SES 2) WATER AND GAS BOND OK 3) FUSES BY TENANT CONTR/BUSHINGS IN CONDUITS 4) HAVE ENGINEER OF RECORD SPECIFY TYPE FUSES FOR MAIN SERVICE DISCONNECT |
|
03/26/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) FUSES NOT INSTALLED YET 2) BUSHINGS REQUIRED AT CONDUIT STUB UP INTO GEAR 352.46 3) LOCK NUTS ON SERVICE EQUIPMENT FACING WRONG DIRECTION 110.3 4) WIRE FILL NOT TO EXCEED 20 PERCENT FOR GUTTER 366.12 5) PIPE BOND CLAMPS TO BE INSTALLED PER LISTING 110.36 6) REVISION FOR SHELL TO BE APPROVED, REOPEN PERMIT 7) CANNOT MIX LOAD WITH SUPPLY CONDUCTORS IN SAME ENCLOSURE PER 230.6 PER CONVERSION WITH ELECTRICIANS |
|
02/16/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK SMALL OFFICES 2ND LEVEL ROUGH WALLS |
|
02/12/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK REMAINDER OF FULL SIZE WALLS |
|
02/10/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK WALLS ROOM 261, EXTERIOR EAST AND NORTH WALL, 2ND FLOOR, ROOM 230 AND 212 |
|
02/02/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK EXTERIOR WALLS 1ST FLOOR |