Permit: T08CM02269

Parcel: 10511061E


Addresses:

160 W WETMORE RD


Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Permit Number - T08CM02269

Inspection Description - ELECTRIC - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
04/15/2010 ELECTRIC - PROGRESS Approved IVRS - Inspection :*
04/07/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1. BE SURE LV COMPLETE ABOVE ABOVE CEILING
ALSO SUPPORT PER NEC. 725-800

2. OK TO CLEAR TEC (CALLED IN TO DENISE @ TEP)
3. CONTR. TO LOCK OUT TAG OUT ELEC. EQUIP.
ONLY AUTHORIZED PERSONNEL TO HAVE ACCESS
4. RECEIVED LETTER FROM ENGINEER OF RECORD TO SPECIFY FUSE AT MAIN SERVICE DISCONNECT.
04/01/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) RECEIVED LETTER OF TORQUE FOR SES
2) WATER AND GAS BOND OK
3) FUSES BY TENANT CONTR/BUSHINGS IN CONDUITS
4) HAVE ENGINEER OF RECORD SPECIFY TYPE FUSES FOR MAIN SERVICE DISCONNECT
03/26/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) FUSES NOT INSTALLED YET
2) BUSHINGS REQUIRED AT CONDUIT STUB UP INTO GEAR 352.46
3) LOCK NUTS ON SERVICE EQUIPMENT FACING WRONG DIRECTION 110.3
4) WIRE FILL NOT TO EXCEED 20 PERCENT FOR GUTTER 366.12
5) PIPE BOND CLAMPS TO BE INSTALLED PER LISTING 110.36
6) REVISION FOR SHELL TO BE APPROVED, REOPEN PERMIT
7) CANNOT MIX LOAD WITH SUPPLY CONDUCTORS IN SAME ENCLOSURE PER 230.6 PER CONVERSION WITH ELECTRICIANS
02/16/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK SMALL OFFICES 2ND LEVEL ROUGH WALLS
02/12/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK REMAINDER OF FULL SIZE WALLS
02/10/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK WALLS ROOM 261, EXTERIOR EAST AND NORTH WALL, 2ND FLOOR, ROOM 230 AND 212
02/02/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK EXTERIOR WALLS 1ST FLOOR