Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/28/2008 | PLUMBING - FINAL | Approved | ||
| 08/27/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PLASTIC TUBING NOT APPROVED DRAINAGE PIPING - SEE NOTE #3 FROM 8/25/08 2. ALL FLOOR SINKS REQUIRE GRATES AND STRAINERS SEE NOTE #1 FROM 8/25/08 3. INSTALL FRANK PATTERN CLEANOUT COVER FOR FLOOR CLEANOUT 4. THERE MAY BE NO SYSTEM VENT BETWEEN FLOW CONTROL VENT AND GREASE TRAP 5. REQUIRE ADDRESSED BACTERIA REPORT |
|
| 08/26/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/25/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. GRATES AND STRAINERS AT FLOOR SINKS 2. FULL AIR GAP AT ALL I.W PIPING 3. ALL I.W PIPING TO BE APPROVED TYPE 4. RPPBP DRAINS TO BE ABLE TO DISCHARGE FULL AMT. 5. FINISH 3 COMP SINK 6. ALL SINKS REQUIRE CLEANOUTS STERILIZATION CERTIFICATION |