Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/26/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/25/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20 ALSO, WALLPAPER MAY BE COMBUSTIBLE 2. REVISED PANEL SCHEDULE TO BE AS PER 408.4 NO ABBREVIATIONS & DISTINGUISHABLE FROM ONE ANOTHER 3. NEED ARC FLASH LABELING AS PER PLANS 4. PLANS CALL FOR NEW SWITCH PANEL 5. INSTALL MAIN BONDING JUMPER MAIN DISCONNECT |