Permit: T08CM02235

Parcel: 12307294C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/26/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/25/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
ALSO, WALLPAPER MAY BE COMBUSTIBLE
2. REVISED PANEL SCHEDULE TO BE AS PER 408.4
NO ABBREVIATIONS & DISTINGUISHABLE FROM ONE ANOTHER
3. NEED ARC FLASH LABELING AS PER PLANS
4. PLANS CALL FOR NEW SWITCH PANEL
5. INSTALL MAIN BONDING JUMPER MAIN DISCONNECT