Permit: T08CM02226

Parcel: 114600340

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T08CM02226

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/17/2009 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
04/16/2009 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
116 -- CLOSET FLANGE IS OK
120 -- CORRECT HEIGHT AND FOULING LEDGE
01/20/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK TO COVER WALLS, INSTALL BACKING AT MS
2. NEED TO INSPECT CLOSET FLANGES AFTER FINISHED FLOOR
3. NOTE RM. 116 CLOSET FLANGE NOT SUPPORTED OR PROPERLY SECURED
4. RM. 120 FLANGE SET ON ROUGH FLOOR AND NOT SECURED
5. CLEAN OUT PLUGS REQUIRE THREAD SEALANT
01/16/2009 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE MIN. TRAP ARM DISTANCE AT WASHER BOX
2. SUPPORT 3" PVC PER T3-2
3. PROVIDE CODE APPROVED SUPPORTS ON PEX
4. INSTALL SAFETY PLATES WHERE PIPING IS LESS
THAN 1 1/4 FROM STUD FACE
12/23/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
P-3 FIXTURES ALONG WEST WALL AND TR 104 -- TEST OK