Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T08CM02226
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/17/2009 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/16/2009 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 116 -- CLOSET FLANGE IS OK 120 -- CORRECT HEIGHT AND FOULING LEDGE |
|
01/20/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK TO COVER WALLS, INSTALL BACKING AT MS 2. NEED TO INSPECT CLOSET FLANGES AFTER FINISHED FLOOR 3. NOTE RM. 116 CLOSET FLANGE NOT SUPPORTED OR PROPERLY SECURED 4. RM. 120 FLANGE SET ON ROUGH FLOOR AND NOT SECURED 5. CLEAN OUT PLUGS REQUIRE THREAD SEALANT |
|
01/16/2009 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE MIN. TRAP ARM DISTANCE AT WASHER BOX 2. SUPPORT 3" PVC PER T3-2 3. PROVIDE CODE APPROVED SUPPORTS ON PEX 4. INSTALL SAFETY PLATES WHERE PIPING IS LESS THAN 1 1/4 FROM STUD FACE |
|
12/23/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* P-3 FIXTURES ALONG WEST WALL AND TR 104 -- TEST OK |