Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/08/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/02/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROTECT M/C CABLE AT EXPOSED SHALLOW STUD 2. SUPPORT M/C CABLE AT CONNECTION TO BOX IN OPENED DRY WALL 3. SUPPORT M/C CABLES 6' INTERVALS 4. NEED LETTER AUTHORIZING USE OF M/C CABLE |