Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM02197
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/22/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK ELECTRIC |
|
07/21/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) NEED ANTI TIP FOR RANGE 2) KITCHEN COUNTER RECEPTACLE TO BE GFCI PROTECTED 3) CANNOT USE EXTENTION CORD FOR DISHWASHER 4) BATH GFI INCORRECTLY WIRED 5) FURNACE PLUG COMING OUT OF WALL 6) PROTECT CONDUCTOR FROM SHARP METAL EDGES-KITCHEN LIGHT 7) GROUND FIXTURE WITH APPROVED HARDWARE-NOT MOUNTING SCREWS 8) PROPERLY GROUND LIGHT FIXTURES 9) FREE UP MOVING PARTS AT SERVICE DISCONNECT |