Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/30/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/28/2008 | ELECTRIC - FINAL | Denied | 1) PLAN SHOWS 20A CB AT SERVICE 2) SCHEDULE 40 PVC TO BE 18" BELOW GRADE 3) GROUND WIRE IN SOLAR METER TO BE COMPLETELY UNDER LUG 4) ACCESS WIRING IN SOLAR METER HITTING WING NUT |