Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T08CM02158
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/13/2009 | FIRE - FINAL | Approved | ||
| 02/24/2009 | FIRE - FINAL | Denied | NEED TO CHANGE PLANS SHOWING EAST PART OF BUILDING(S) AS NOT SPRINKLERED. NEED TO SHOW WHERE FIRE SEPARATION WALL BETWEEN SPRINKLERED AND NON-SPRINKLERED (all openings like doors rated) |
|
| 01/05/2009 | FIRE - FINAL | Denied | Need up to date fire sprinkler inspection done, last one on file 10/2006. This is done yearly. Need 5 year fire alarm check valve inspection done, nothing on file. Remove thumb latch dead bolt lock from panic hardware door. Add sprinkler coverage under canopies outside. |