Permit: T08CM02158

Parcel: 11103017E


Addresses:

3801 E KLEINDALE RD


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T08CM02158

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/13/2009 FIRE - FINAL Approved
02/24/2009 FIRE - FINAL Denied NEED TO CHANGE PLANS SHOWING EAST PART OF BUILDING(S) AS NOT SPRINKLERED.
NEED TO SHOW WHERE FIRE SEPARATION WALL BETWEEN SPRINKLERED AND NON-SPRINKLERED (all openings like doors rated)
01/05/2009 FIRE - FINAL Denied Need up to date fire sprinkler inspection done, last one on file 10/2006. This is done yearly.
Need 5 year fire alarm check valve inspection done, nothing on file.
Remove thumb latch dead bolt lock from panic hardware door.
Add sprinkler coverage under canopies outside.