Permit: T08CM02158

Parcel: 11103017E


Addresses:

3801 E KLEINDALE RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM02158

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/13/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/09/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
WAITING ON LETTER FROM ENGINEER FOR LIGHTING
02/02/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
ROOF:
1. PROPERLY INSTALL FITTINGS WITH ALL PARTS
2. BOND DISCONNECT ENCLOSURE
3. LABEL DISCONNECT

BUILDING:
1. FINISH PREVIOUS ITEMS 1, 2, 7, 9 AND 10
01/26/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
NO WORK PROGRESS
PLEASE PAY REFEE BEFORE NEXT INSPECTION
01/05/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOXES MORE THAN 1/4" - 314.20 & MORE THAN 1/8" - 314.21
2. LIGHTS NOT SWITCHED AS PER PLANS
3. PANEL DIRECTORIES NOT DISTINGUISHABLE FROM ONE ANOTHER -- 408.4
4. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM BOTTOM OF PANELS
5. SEPARATE GROUNDS & NEUTRALS AT SUB-PANEL 250.24
6. BOND PANEL ENCLOSURE
7. GROUNDED CONDUCTOR TO BE WHITE ENTIRE LENGTH 200
8. BATHROOM RECEPTACLES NOT TO BE ON KITCHEN GFCI CIRCUIT
9. WATER HEATER TO HAVE DISCONNECTING MEANS
10. CORDS NOT ALLOWED ABOVE CEILING 400.7 & 400.8
11. NORTH TWO-THIRDS OF BUILDING INACCESSIBLE DUE TO FLOOR PAINTING
12. LABEL PANEL COVERS ON OUTSIDE TO DISTINGUISH
13. PLEASE PROVIDE ROOF ACCESS