Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM02158
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/13/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/09/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* WAITING ON LETTER FROM ENGINEER FOR LIGHTING |
|
| 02/02/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ROOF: 1. PROPERLY INSTALL FITTINGS WITH ALL PARTS 2. BOND DISCONNECT ENCLOSURE 3. LABEL DISCONNECT BUILDING: 1. FINISH PREVIOUS ITEMS 1, 2, 7, 9 AND 10 |
|
| 01/26/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio NO WORK PROGRESS PLEASE PAY REFEE BEFORE NEXT INSPECTION |
|
| 01/05/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOXES MORE THAN 1/4" - 314.20 & MORE THAN 1/8" - 314.21 2. LIGHTS NOT SWITCHED AS PER PLANS 3. PANEL DIRECTORIES NOT DISTINGUISHABLE FROM ONE ANOTHER -- 408.4 4. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM BOTTOM OF PANELS 5. SEPARATE GROUNDS & NEUTRALS AT SUB-PANEL 250.24 6. BOND PANEL ENCLOSURE 7. GROUNDED CONDUCTOR TO BE WHITE ENTIRE LENGTH 200 8. BATHROOM RECEPTACLES NOT TO BE ON KITCHEN GFCI CIRCUIT 9. WATER HEATER TO HAVE DISCONNECTING MEANS 10. CORDS NOT ALLOWED ABOVE CEILING 400.7 & 400.8 11. NORTH TWO-THIRDS OF BUILDING INACCESSIBLE DUE TO FLOOR PAINTING 12. LABEL PANEL COVERS ON OUTSIDE TO DISTINGUISH 13. PLEASE PROVIDE ROOF ACCESS |