Permit: T08CM02158

Parcel: 11103017E


Addresses:

3801 E KLEINDALE RD


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T08CM02158

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
02/13/2009 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
12/03/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO TILE
12/02/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT WIRE NEED FOR EXIT LIGHT
2. SUPPORT MC AS PER 300.11

UNNECESSARY INSPECTIONS MAY RESULT IN A REFEE
11/26/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) FINISH DEMO & REMOVAL OF TEMP LIGHTING
2) FINISH ITEMS #1, 2 & 6 PREVIOUS INSPECTION
3) OK AFTER CORRECTIONS
11/24/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. FINISH SUPPORTING MC AND CONDUITS ABOVE PANEL
2. SUPPORT OR REMOVE VDV CABLING AS
PER 725.3 & 24, 800.3 & 24, 300.11
3. UNCOIL M/C CABLES FROM AROUND RAFTERS
4. CONDUIT COUPLING IS SEPARATING & RUN HAS MORE
THAN 360 DEG. IN ENTIRE RUN
5. SEAL UNUSED CONDUIT OPENINGS
6. SUPPORT ELECTRIC AS PER 300.11
7. BOX OVERFILLED
11/20/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
CANCELED -- BY SUPERINTENDENT THORUGH JIM M.