Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T08CM02158
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/13/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 12/03/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO TILE |
|
| 12/02/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT WIRE NEED FOR EXIT LIGHT 2. SUPPORT MC AS PER 300.11 UNNECESSARY INSPECTIONS MAY RESULT IN A REFEE |
|
| 11/26/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FINISH DEMO & REMOVAL OF TEMP LIGHTING 2) FINISH ITEMS #1, 2 & 6 PREVIOUS INSPECTION 3) OK AFTER CORRECTIONS |
|
| 11/24/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FINISH SUPPORTING MC AND CONDUITS ABOVE PANEL 2. SUPPORT OR REMOVE VDV CABLING AS PER 725.3 & 24, 800.3 & 24, 300.11 3. UNCOIL M/C CABLES FROM AROUND RAFTERS 4. CONDUIT COUPLING IS SEPARATING & RUN HAS MORE THAN 360 DEG. IN ENTIRE RUN 5. SEAL UNUSED CONDUIT OPENINGS 6. SUPPORT ELECTRIC AS PER 300.11 7. BOX OVERFILLED |
|
| 11/20/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* CANCELED -- BY SUPERINTENDENT THORUGH JIM M. |