Permit: T08CM02158

Parcel: 11103017E


Addresses:

3801 E KLEINDALE RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM02158

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/13/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/29/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROOMS 1 & 8 SUBJECT TO LETTER

1. OUTLETS ON EXTERIOR WALL DIFFER FROM PLANS
NEED LETTER OK'ing CONDITION ON SITE
09/25/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROOMS 2-7
09/24/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
FINISH PREVIOUS ITEMS 1, 2 AND 4 FROM 9/22/08 INSP.
09/22/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CORRECT SUPPORT CONDUITS ABOVE PANEL
2. M/C AND CONDUIT NOT TO BE SUPPORTED TO OTHER WIRING METHODS
3. PROTECT M/C INSIDE OF STUD CHANNELS
4. USE APPROVED STRAPS FOR M/C
5. FILL UNUSED OPENINGS
6. CORRECTLY MOUNT BOXES
7. NO MORE THAN 360 DEG. IN CONDUIT RUNS