Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM02158
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/13/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/29/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROOMS 1 & 8 SUBJECT TO LETTER 1. OUTLETS ON EXTERIOR WALL DIFFER FROM PLANS NEED LETTER OK'ing CONDITION ON SITE |
|
| 09/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROOMS 2-7 |
|
| 09/24/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* FINISH PREVIOUS ITEMS 1, 2 AND 4 FROM 9/22/08 INSP. |
|
| 09/22/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CORRECT SUPPORT CONDUITS ABOVE PANEL 2. M/C AND CONDUIT NOT TO BE SUPPORTED TO OTHER WIRING METHODS 3. PROTECT M/C INSIDE OF STUD CHANNELS 4. USE APPROVED STRAPS FOR M/C 5. FILL UNUSED OPENINGS 6. CORRECTLY MOUNT BOXES 7. NO MORE THAN 360 DEG. IN CONDUIT RUNS |