Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM02141
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/10/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
10/08/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. MISSING EM LIGHT BACK ROOM 2. NEED TO PROTECT #3 CONDUCTORS FEEDING 120/280V PANEL. OK TO INSTALL 3 POLE 100A & BACK FEED IF BREAKER MECHANICALLY SECURED TO PANEL 3. BREAKERS IN PANEL TO BE SIEMENS 4. ALL OTHER PREVIOUS INSPECTION ITEMS CORRECTED |
|
10/06/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FINISH CHANGING OUT LIGHTS STORE ROOM 2. INSTALL EXTENSION OF RECEPT. BOX MORE THAN 1/4" BACK 3. HAVE 30 KVA XFMR FEEDING 200 AMP BREAKER IN EXISTING PANEL WITH #3 CONDUCTORS 4. CLOSE OPEN KNOCKOUT XFMR 5. FINISH ROOF WORK 6. EM LIGHTS NOT PER PLAN. CIRCUITING NOT PER PLAN. EXIT NOT WORKING. |