Permit: T08CM02141

Parcel: 12801005H

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/10/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/08/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. MISSING EM LIGHT BACK ROOM
2. NEED TO PROTECT #3 CONDUCTORS FEEDING 120/280V PANEL. OK TO INSTALL 3 POLE 100A & BACK FEED IF BREAKER MECHANICALLY SECURED TO PANEL
3. BREAKERS IN PANEL TO BE SIEMENS
4. ALL OTHER PREVIOUS INSPECTION ITEMS CORRECTED
10/06/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. FINISH CHANGING OUT LIGHTS STORE ROOM
2. INSTALL EXTENSION OF RECEPT. BOX MORE THAN 1/4" BACK
3. HAVE 30 KVA XFMR FEEDING 200 AMP BREAKER IN EXISTING PANEL WITH #3 CONDUCTORS
4. CLOSE OPEN KNOCKOUT XFMR
5. FINISH ROOF WORK
6. EM LIGHTS NOT PER PLAN. CIRCUITING NOT PER PLAN. EXIT NOT WORKING.