Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/24/2008 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* | |
| 07/23/2008 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO PLUMB WRAP ALL ABS PIPING IN CONCRETE 2) NEED TWO GROUND RODS FOR NEW SERVICE 3) NEED TO BOND GAS/METALLIC WATER LINES 4) NEED ADDRESS ON PANEL 5) MAIN DISCONNECT TO HIGH 6'-7" MAX 6) NEED TO PLUG ALL UNUSED OPENINGS AT SERVICE 7) NEED MIN 18" OF FREE CONDUCTOR AT WEATHER HEAD |
|
| 07/22/2008 | EXCAVATION/LAYOUT REBAR & ZON | Not ready for Inspection | IVRS - Inspection :* 1) INSTALL REBAR PER PLAN 2) SOIL PIPE FOR LAUNDRY OK 3) GAS YARD LINE TO LAUNDRY ROOM OK |