Permit: T08CM02139

Parcel: 126160810

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
07/24/2008 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
07/23/2008 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED TO PLUMB WRAP ALL ABS PIPING IN CONCRETE
2) NEED TWO GROUND RODS FOR NEW SERVICE
3) NEED TO BOND GAS/METALLIC WATER LINES
4) NEED ADDRESS ON PANEL
5) MAIN DISCONNECT TO HIGH 6'-7" MAX
6) NEED TO PLUG ALL UNUSED OPENINGS AT SERVICE
7) NEED MIN 18" OF FREE CONDUCTOR AT WEATHER HEAD
07/22/2008 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*
1) INSTALL REBAR PER PLAN
2) SOIL PIPE FOR LAUNDRY OK
3) GAS YARD LINE TO LAUNDRY ROOM OK