Permit: T08CM02132

Parcel: 121080080


Addresses:

6211 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
03/27/2009 FIRE - FINAL Approved
01/08/2009 FIRE - FINAL Partial Approval Partial approval. Conditional C of O. 1/08/09.
Per Dave Mann, OK to open for business provided items 12, 13 and 14 be completed by estimated time. ( 4 weeks)
08/21/2008 FIRE - FINAL Denied 1.) Repair emergency back-up lights.
a.) over main exit
b.) by handi-cap restroom
c.) hallway leading out from principals office.
2.) Cover plates
a.) in the "red room", x2
b.) on the wall, hallway area.
c.) soffit, principals office.
3.) Replace broken mirror.
a.) classroom area.
b.) next to west exit door, main floor area.
4.) Cover openings in walls or ceiling.
a.) wall, principals office.
b.) soffit, principals office.
c.) next to electrical panel by walk-in closet.
d.) ceiling overmop sink.
e.) Larry's office, ceiling, in the electrical closet.
5.) Missing escutcheon in bathroom.
6.) Electrical plugs for electrical panel "K", next to walk-in cooler.
7.) Provide key to unlock doors for the "walk-in cooler" and the "Liquor Room".
8.) Lable riser room door "RISER ROOM". 3 to 6 inch lettering.
9.) Provide key for access into the riser room (Knox-Box).
10 ) Clear accumulation of combustible storage in riser room area and in the hot water heater room.
11.) Need annual sprinkler inspection.
12.) Need 5 year check valve inspection.
13.) Need fire alarm system installed and inter-connected to sprinkler system.
14.) Require to submitt plans and permits for fire alarm system.