Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/30/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/29/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* ROOF: 1. CURRENTLY IDENTIFY UNGROUNDED CONDUCTOR PANEL: 1. NEED MFG HOLD DOWN |
|
| 07/28/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. MISSING COVER PLATE 2. BOXES MORE THAN 1/4" - 314.20 3. CLEAN EXCESS DIRT FROM BOTTOM OF PANEL 4. BACK FED MAIN TO HAVE MANUFACTURES HOLD DOWN 5. CHECK ROOF NEXT TIME |