Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/30/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/23/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* BOX OVERFILLED - JUNCTION BOX BEHIND DISHWASHER OK WALLS |
|
| 07/22/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. DO NOT BUNDLE NM CABLES IN HOLE & STAPLE 2. USE APPROVED SIZE FITTING TO SECURE NM CABLE 3. USE APPROVED & LISTED JUNCTION BOX NOT OLD PANEL 4. UNDERGROUND DONE & COVERED WITHOUT INSPECTIONS |
|
| 06/30/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HAVE SEVERAL CODE VIOLATIONS IN UNITS 2. HAVE WORK COVERED BEFORE APPROVAL 3. PLANS DO NOT REFLECT ACTUAL SCOPE OF WORK 4. NEED HARD WIRED SMOKE DETECTORS 5. NEED LICENSED ELECTRICAL CONTRACTOR TO GO THROUGH UNITS AND BRING TO CODE BEFORE CALLING FOR INSPECTIONS ALSO, PLANS AND PERMITS TO BE REVISED TO REFLECT ACTUAL SCOPE OF WORK. |