Permit: T08CM02121

Parcel: 124082420


Addresses:

55 N CHERRY AV 4


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM02121

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/30/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/23/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
BOX OVERFILLED - JUNCTION BOX BEHIND DISHWASHER

OK WALLS
07/22/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. DO NOT BUNDLE NM CABLES IN HOLE & STAPLE
2. USE APPROVED SIZE FITTING TO SECURE NM CABLE
3. USE APPROVED & LISTED JUNCTION BOX NOT OLD PANEL
4. UNDERGROUND DONE & COVERED WITHOUT INSPECTIONS
06/30/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HAVE SEVERAL CODE VIOLATIONS IN UNITS
2. HAVE WORK COVERED BEFORE APPROVAL
3. PLANS DO NOT REFLECT ACTUAL SCOPE OF WORK
4. NEED HARD WIRED SMOKE DETECTORS
5. NEED LICENSED ELECTRICAL CONTRACTOR TO GO THROUGH UNITS AND BRING TO CODE BEFORE CALLING FOR INSPECTIONS ALSO, PLANS AND PERMITS TO BE REVISED TO REFLECT ACTUAL SCOPE OF WORK.