Permit: T08CM02112

Parcel: 124082420


Addresses:

55 N CHERRY AV 3

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/11/2008 ELECTRIC - FINAL Approved
08/07/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) BREAKERS NOT CORRECTLY LABELED TO WHAT THEY CONTROL
2) FINISH PREVIOUS ITEMS
3) DISCONNECT (MAIN) NOT LABELED
4) DISCONNECT (MAIN) NOT WORKING PROPERLY
08/05/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOXES MORE THAN 1/4" - 314.20
2. A PERMANENT CIRCUIT DIRECTORY AS PER 408.4
3. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM INSIDE OF PANEL
4. A CONNECTOR IS NEEDED AT FAN BOX & FILL UNUSED OPENING
5. USE APPROVED HARDWARE FOR MOUNTING DEVICES

CHECK ROOF NEXT TIME