Permit: T08CM02110

Parcel: 124082420


Addresses:

55 N CHERRY AV 3


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM02110

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/29/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/11/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BATHROOM CIRCUITS NOT TO BE ON SAME CIRCUITS AS BEDROOMS
2) A RE-INSPECTION FEE WILL BE ASSESED NEXT INSPECTION IF NO COMPLIANCE
09/04/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
See notes last inspection (2)
A re-inspection fee is assessed
08/21/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ALL BEDROOM OUTLETS TO BE ARC FAULT PROTECTED PER 210 NEC
04/20/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ARC FAULTS NOT TRIPPING UNDER TEST