Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T08CM02106
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/24/2008 | MECHANICAL - FINAL | Approved | ||
07/23/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE APPROVED FILTER RACK FROM MANUFACTURER |
|
07/21/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FLUE CONNECTOR MUST BE MIN. 6" AWAY FROM COMBUSTIBLE MATERIAL 2. PVC MUST BE PRIMED 3. CONDENSATE DRAIN NOT PROPERLY RUN 4. GAS PIPING NOT CONNECTED 5. PROVIDE APPROVED FILTER RACK 6. PROVIDE SCREW IN ELECTRICAL BOX 7. REMOVE ALL FOIL TAPE FROM FLUE |