Permit: T08CM02106

Parcel: 124082420


Addresses:

55 N CHERRY AV 3


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T08CM02106

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/24/2008 MECHANICAL - FINAL Approved
07/23/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PROVIDE APPROVED FILTER RACK FROM MANUFACTURER
07/21/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. FLUE CONNECTOR MUST BE MIN. 6" AWAY FROM COMBUSTIBLE MATERIAL
2. PVC MUST BE PRIMED
3. CONDENSATE DRAIN NOT PROPERLY RUN
4. GAS PIPING NOT CONNECTED
5. PROVIDE APPROVED FILTER RACK
6. PROVIDE SCREW IN ELECTRICAL BOX
7. REMOVE ALL FOIL TAPE FROM FLUE