Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM02106
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/24/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* |
|
07/24/2008 | ELECTRIC - FINAL | Approved | ||
07/23/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. ADDRESS AND UNIT LABELS ROOF: 1. TIGHTEN LOOSE FITTINGS 2. MAINTAIN WORKING CLEARANCES 3. CORRECTLY IDENTIFY CONDUCTOR 4. SUPPORT CARFLEX OFF ROOF |
|
07/21/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. APPR. EXTENDER RINGS NEEDED FOR BOXES - 314.20 2. SECURE DEVICES IN WALLS 3. PROTECT BULBS IN CLOSET 4. EXHAUST FAN TO BE FOR WET LOCATION 5. PLEASE 7' MINIMUM FAN BLADE MINIMUM HEIGHT - INSTRUCTIONS LIST |