Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/15/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/14/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* SUPPORT ROOF DISCONNECT OTHER THAN ROOF CAP |
|
| 08/13/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK LIGHTS & FANS - CLOSE PANEL 1. CHECK MAIN SERVICE |
|
| 08/08/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* FINISH PREVIOUS |
|
| 08/07/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20 2) LABEL CIRCUIT DIRECTORY PER 408.4 3) GROUNDING EQUIPMENT CONDUCTORS TO BE SAME SIZE IF DBL LUGGED 4) PROPERLY GROUND FIXTURES ROOF: GROUND JUNCTION BOX AND DRAIN AND CORRECTLY IDENTIFY CONDUCTOR 5) MAIN DISCONNECT NOT WORKING PROPERLY 6) MAIN NOT LABELED |