Permit: T08CM02094

Parcel: 124082420


Addresses:

55 N CHERRY AV 1


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM02094

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/15/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/14/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
SUPPORT ROOF DISCONNECT OTHER THAN ROOF CAP
08/13/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK LIGHTS & FANS - CLOSE PANEL

1. CHECK MAIN SERVICE
08/08/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
FINISH PREVIOUS
08/07/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
2) LABEL CIRCUIT DIRECTORY PER 408.4
3) GROUNDING EQUIPMENT CONDUCTORS TO BE SAME SIZE IF DBL LUGGED
4) PROPERLY GROUND FIXTURES ROOF: GROUND JUNCTION BOX AND DRAIN AND CORRECTLY IDENTIFY CONDUCTOR
5) MAIN DISCONNECT NOT WORKING PROPERLY
6) MAIN NOT LABELED