Permit: T08CM02090

Parcel: 124082420


Addresses:

55 N CHERRY AV 1


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM02090

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/04/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/01/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
A REINSPECTION FEE WILL BE ASSESSED IF UNNECESSARY INSPECTION ARE CALLED IN
07/31/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. FINISH PREVIOUS ITEMS

ROOF:
1. DUCT TAPE IS NOT AN APPROVED SUPPORTING METHOD
2. GREEN OR BARE ENTIRE LENGTH 250.119
3. LABEL UNIT
07/30/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. USE WIRE NUTS PER LISTING FOR NUMBER OF CONDUCTORS
2. LABEL PANEL AS PER 408.4