Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/27/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/25/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. UNGROUNDED RECEPTACLES TO BE AS PER 406.3 (D) 2. CLEAN EXCESS PAINT AND FOREIGN MATERIAL FROM DEVICE TERMINALS - 110.12 3. BOND PANEL ENCLOSURE 4. BOXES MORE THAN 1/4" IN NON-COMBUSTIBLES - 314.20 5. INSTALL SMOKE DETECTOR AS PER MANUFACTURES INSTRUCTIONS |