Permit: T08CM02063

Parcel: 12809006B


Addresses:

5409 E 22ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
07/28/2011 ELECTRIC - UNDERGROUND Approved #4 TO GROUND RING OK
09/30/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
NEED TO REVISE PLANS FOR ALL CHANGES
NEEDS TO GO BACK THROUGH PLAN REVIEW
A LETTER IS NOT ACCEPTABLE
RECALL WHEN PLANS REVISED AND APPROVED
09/09/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK PVC U.G
2. PLAN CALLS FOR 3/0 GROUND TO TIE INTO EXISTING GROUND RING
3. IS THERE PROPER WORKING CLEARANCE AROUND THE GENERATOR? IT APPEARS TO BE TIGHT.