Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/07/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CLEAN SURFACE UNDER LUG 250.12 2) GROUND ROD TO BE 6' MINIMUM 250.52 & 64 3) RECALL AFTER CROSS OVER |
|
| 08/05/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | 1. ABOVE GRADE TO BE SCHED. 80 - CITY AMENDMENTS 2. NEED 2ND GROUND ROD & GROUNDING ELECTRODE CONDUCTOR 3. SECURE RISER - LOCKNUT 4. NEED BUSHING 352.46 & 300.4 |