Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T08CM02046
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/30/2009 | PLUMBING - ROUGH, SOIL | Approved | EXCEPT FOR NOTE #1 FROM 07/10/2009 ALL OF CORRECTIONS MADE OK OK TO COVER UNDERGROUND |
|
07/10/2009 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | 1) GAS NOT INSTALLED PER PLAN. PROVIDE ACCESS TO P.O.C. TO EXISTING AND HAVE RED LINES READY AT TIME OF INSPECTION 2) CONNECTIONS TO EXISTING SEWER ARE COVERED. MUDDY SOILS INDICATE A LEAK 3) 3" ABS MAY NOT EXTEND UPSTREAM OF THE 3" FLOOR CLEANOUT WITHOUT AN ADDITIONAL FULL SIZE CLEANOUT 4) WATER PIPING NOT INSTALLED PER PLAN. PLAN CALLS FOR TYPE "L" COPPER 5) ALL CHANGES TO THE PLAN REQUIRE AT LEAST RED LINES TO BE AVAILABLE AT THE TIME OF THE INSPECTION |
|
07/09/2009 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE APPROVED PLANS, CORRECT SIZING 2) INSTALL ABV SLAB TEST FITTINGS OR PLAN TO RE-TEST 3) REMOVE ROCKS |