Permit: T08CM02046

Parcel: 12901036B


Addresses:

300 S TUCSON BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/12/2010 ELECTRIC - INTERMEDIATE Approved PER EL FINAL
12/10/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ITEMS ON LIST AND CEILING OK
2) EXCEPT FIRE ALARM
3) CALL BACK FOR FINAL
12/02/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
2036 2090
11/13/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) ANSWERED QUESTIONS
08/18/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS
2) PANEL TO HAVE APPROVED COVERS-1 PER PANEL, SAME THICKNESS, NO TERMINATIONS THRU COVERS AND LABELED
08/17/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) USE APPROVED SECURING MEANS
2) PROTECT CABLES PER 300.4
3) M/C TO TERMINATE TO ENCLOSURE
08/13/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED TO BE 1 1/4 FROM EDGE OF STUD
08/10/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
07/29/2009 ELECTRIC - INTERMEDIATE Partial Approval OK SCHEDULED 80 PVC UNDER SLAB PER ENGINEER LETTER
07/10/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) PLANS STATE PVC SHCEDULE 40 NOT ALLOWED