Permit: T08CM02031

Parcel: 11105026F

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/22/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/17/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS

*M/C TO BE INDEPENDENTLY SUPPORTED 300.11
VDV CABLING AS PER 725.24 & 800.24
09/15/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MC CANNOT TERMINATE INTO PLASTIC NAIL ON BOX,
USE APPROVED BOX & FITTINGS