Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T08CM02023
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/23/2009 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
06/12/2009 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
01/12/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* GAS PRESSURE TEST OK CORRECTIONS MADE OK OK TO COVER ALL AREAS STILL NEED TO SEE CLOSET FLANGES AND ALL OTHER UNMADE CONNECTIONS I.E. FLOOR CLEANOUT, MOP SINK, ETC. |
|
01/08/2009 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* SEE NOTE NUMBER THREE FROM 12/30/08 ARMAFLEX REQUIRES MITERED JOINTS, LAGGING ADHESIVE AND TAPE. * CONTINUAL NOT READY WILL RESULT IN REINSPECTION FEE |
|
12/30/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) SEE P1 PLUMBING SPECIFICATIONS NOTE NUMBER 6 INSULATION 2) NOT INSULATED PER PLAN 3) NOT INSULATED TO MINIMUM STANDARD |
|
12/16/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. TEST ON DWV AND GAS OK 2. REDLINE GAS ROUTING CHANGE USE APPROVED CLAMPS IN WALL 3. CORRECT SLOPE ON TRAP ARM SUPPORT, PROTECT ABS FROM SHARP EDGES 4. WATER PIPING NOT SIZED PER PLAN 5. REMOVE EXCESS FLUX FROM CW AND HW 6. VENT NOT THRU ROOF 7. NAIL PLATES; BACKING |