Permit: T08CM02023

Parcel: 10821018Y

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T08CM02023

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/23/2009 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
06/12/2009 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/12/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
GAS PRESSURE TEST OK
CORRECTIONS MADE OK
OK TO COVER ALL AREAS
STILL NEED TO SEE CLOSET FLANGES AND ALL OTHER UNMADE CONNECTIONS I.E. FLOOR CLEANOUT, MOP SINK, ETC.
01/08/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
SEE NOTE NUMBER THREE FROM 12/30/08
ARMAFLEX REQUIRES MITERED JOINTS, LAGGING ADHESIVE AND TAPE.

* CONTINUAL NOT READY WILL RESULT IN REINSPECTION FEE
12/30/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) SEE P1 PLUMBING SPECIFICATIONS NOTE NUMBER 6 INSULATION
2) NOT INSULATED PER PLAN
3) NOT INSULATED TO MINIMUM STANDARD
12/16/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. TEST ON DWV AND GAS OK
2. REDLINE GAS ROUTING CHANGE
USE APPROVED CLAMPS IN WALL
3. CORRECT SLOPE ON TRAP ARM
SUPPORT, PROTECT ABS FROM SHARP EDGES
4. WATER PIPING NOT SIZED PER PLAN
5. REMOVE EXCESS FLUX FROM CW AND HW
6. VENT NOT THRU ROOF
7. NAIL PLATES; BACKING