Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM02023
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/23/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/12/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* PLEASE VERIFY LISTING AND LABELING OF ALL KITCHEN EQUIPMENT AND FOOD SERVICE EQUIPMENT |
|
06/09/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. POST BOND FOR TEMP POWER FOR TEST 2. ARRANGE CONDUCTORS AT SERVICE EQUIP. TO COMPLY WITH 250.6 NEC 3. 125V KITCHEN OUTLETS PER 210.8 NEC (GFI) 4. HOW ARE YOU GOING TO TERMINATE NEUTRAL IN TERM CAN AT SERVICE? |